Monday 12 September 2016

Check CB Anti Pumping Function / Trip Free Function

Check CB Anti Pumping Function / Trip Free Function {at local and
remote position) and (at test and service position)}

Step 1: Ensure Gas, Air and DC Supply is normal for the CB under test.

Step 2: Close the Breaker Electrically and Hold the Control Switch in
‘CLOSE’ position.

Step 3: Trip the Breaker by externally extending the DC Supply to Trip
Circuit. (Not by any trip relays which is used for close interlock)

Step 4: Observe the Breaker to ‘TRIP’ and remain in ‘OPEN’ position &
Does not close.

Step 5: Thus Anti Pumping function found working with the above
Sequence.

No comments:

Post a Comment

Fiber optic cable specification for line differential protection in substation

  Common Question and Answer? 1. what is difference between single mode and multimode Fiber? Single mode means the fiber enables one type of...